Q . Reader Interface show 'Communication Down'.
  • Check Door Interface communication status (Green & Yellow LED should blink).
  • Check wiring termination of C+/C- between Door Interface and Reader Interface. Might cause by wrong termination.
  • Q . Green & Yellow LED not blinking or either one of the LED always light ON.
  • Check wiring termination of C+/C- between Door Interface and Reader Interface. Might cause by wrong termination.
  • Change communication IC (75HVD3082). Might cause by faulty IC.
  • Q . No transaction return/ FEP down.
  • Check Software Setting. [FEP Port 0]/ [FEP Port1] should assign with correct portNo. Default will set to NOT USE.
  • Check Alarm Processing-> FEP setting, [Installed] mode should be YES. Default will set to NO.
  • Ensure the CTA Controller assign with correct DIP address.
  • Check on PCI-FEP should have minimum green LED blink from time to time. Indicated signal send out.
  • Q . Configured Events not functional.
  • Re-check to the Event program settings. Ensure correct logic applied.
  • Perform Event download once again. Goto Reload Settings to FEP-> Event Program Lists.
  • Q . Sensor/ Input DO NOT functional
  • Check to the RED LED status. RED blink/ constant to indicate INPUT point opened.
  • Noted that 3.3K Ohm resistor should series for NC connection; Parallel for NO connection.
  • Check to connectivity & correct value/ non defect of resistor.
  • Q . Output not trigger
  • Ensure on-board relay trigger. Check to the NO & Comm connectivity during trigger mode. Red LED should ON.
  • Check to the Event settings. Observe to Constant/ Pulse method applied.
  • Q . Unable to Acknowledge PC Alarm Beeper.
  • Each point of INPUT should perform Acknowledge before to call PC Alarm beeper acknowledge.
  • Q . Perform Total Reload  Return Error Message
  • No Gate Controller Support, this required Gate Controller to supported. Click OK & Ignore to the message.